NEC Article 250 - Grounding and Bonding
Educational Notice: This content provides interpretations and summaries of NEC Article 250. For official code text, please refer to NFPA 70 - National Electrical Code. All content is for educational purposes and should not replace professional judgment or official code consultation.
Overview
NEC Article 250 establishes the requirements for grounding and bonding of electrical systems and equipment. This article is fundamental to electrical safety, providing protection against electrical shock, fire, and equipment damage.
Key Concepts
Grounding vs. Bonding
- Grounding: Connection to earth through a grounding electrode system
- Bonding: Connection between metallic parts to ensure electrical continuity and conductivity
Safety Alert: Proper grounding and bonding are critical for electrical safety. Improper installations can result in electrical shock, electrocution, or fire.
Most Referenced Sections
250.66 - Size of Alternating-Current Grounding Electrode Conductor
Determines the minimum size of the grounding electrode conductor based on the service entrance conductor size.
Grounding Electrode Conductor Sizing Table
Service Entrance Conductor Size | Grounding Electrode Conductor Size |
---|---|
2 AWG or smaller | 8 AWG |
1 AWG or 1/0 AWG | 6 AWG |
2/0 or 3/0 AWG | 4 AWG |
Over 3/0 AWG through 350 kcmil | 2 AWG |
Over 350 kcmil through 600 kcmil | 1/0 AWG |
Over 600 kcmil through 1100 kcmil | 2/0 AWG |
250.122 - Size of Equipment Grounding Conductors
One of the most frequently referenced tables in electrical work, establishing minimum equipment grounding conductor sizes.
Equipment Grounding Conductor Sizing Table
Overcurrent Device Rating | Copper EGC Size | Aluminum EGC Size |
---|---|---|
15 A | 14 AWG | 12 AWG |
20 A | 12 AWG | 10 AWG |
30 A | 10 AWG | 8 AWG |
40 A | 10 AWG | 8 AWG |
60 A | 10 AWG | 8 AWG |
100 A | 8 AWG | 6 AWG |
200 A | 6 AWG | 4 AWG |
300 A | 4 AWG | 2 AWG |
400 A | 3 AWG | 1 AWG |
500 A | 2 AWG | 1/0 AWG |
600 A | 1 AWG | 2/0 AWG |
Pro Tip: When circuit conductors are increased in size for voltage drop considerations, the equipment grounding conductor must be proportionally increased per 250.122(B).
Grounding Systems
250.20 - Alternating-Current Systems to Be Grounded
Systems that must be grounded:
- Single-phase, 2-wire: 120V systems
- Single-phase, 3-wire: 120/240V systems
- Three-phase, 4-wire wye: 208Y/120V, 480Y/277V systems
250.24 - Grounding Service-Supplied Alternating-Current Systems
Service Grounding Requirements:
- Grounded conductor: Must be connected to grounding electrode
- Equipment grounding: All service equipment must be grounded
- Grounding electrode conductor: Sized per 250.66
250.50 - Grounding Electrode System
All available grounding electrodes must be bonded together:
- Metal underground water pipe
- Metal frame of building/structure
- Concrete-encased electrode (Ufer ground)
- Ground ring
- Rod and pipe electrodes
- Plate electrodes
Equipment Grounding
250.118 - Types of Equipment Grounding Conductors
Acceptable equipment grounding conductors:
- Copper, aluminum, or copper-clad aluminum conductor
- Rigid metal conduit (RMC)
- Intermediate metal conduit (IMC)
- Electrical metallic tubing (EMT)
- Flexible metal conduit (FMC) - limited conditions
- Liquidtight flexible metal conduit (LFMC) - limited conditions
- Armor of Type AC cable
- Copper sheath of mineral-insulated cable
250.134 - Equipment Fastened in Place or Connected by Permanent Wiring Methods
Fixed equipment grounding methods:
- Equipment grounding conductor
- Grounded circuit conductor (limited applications)
- Raceway system serving as equipment grounding conductor
Bonding Requirements
250.92 - Services
Service equipment bonding requirements:
- Bonding jumpers: Connect service raceways and enclosures
- Main bonding jumper: Connects grounded conductor to equipment grounding system
- Size: Per Table 250.66 based on service conductors
250.94 - Bonding for Other Systems
Requirements for bonding:
- Communications systems
- CATV systems
- Network-powered broadband systems
- Intersystem bonding termination required
250.104 - Bonding of Piping Systems and Exposed Structural Steel
Metal Water Piping:
- Interior metal water piping: Must be bonded to service equipment
- Bonding conductor size: Per Table 250.66
- Connection points: Near service equipment entrance
Gas Piping:
- CSST systems: Require bonding per manufacturer instructions
- Rigid gas piping: Bonding may be required by local codes
Safety Alert: Never use gas piping as a grounding electrode. Gas piping must be bonded but cannot serve as part of the grounding electrode system.
Special Applications
250.146 - Connecting Receptacle Grounding Terminal to Box
Methods for grounding receptacles:
- Equipment grounding conductor: Direct connection to receptacle
- Self-grounding receptacles: Listed devices with grounding contact
- Grounding pigtail: When box is grounded through raceway
250.148 - Continuity and Attachment of Equipment Grounding Conductors to Boxes
Requirements for box grounding:
- Splicing: Equipment grounding conductors must be spliced with approved methods
- Connection to box: Direct connection required for metal boxes
- Pigtail method: Acceptable for maintaining continuity
Calculation Examples
Example 1: Service Grounding Electrode Conductor
Service: 200A with 3/0 AWG copper service entrance conductors Grounding electrode conductor: 4 AWG copper (per Table 250.66)
Example 2: Equipment Grounding Conductor
Circuit: 30A branch circuit with 10 AWG conductors Equipment grounding conductor: 10 AWG copper (per Table 250.122)
Example 3: Upsized Circuit with Voltage Drop Compensation
Original circuit: 20A with 12 AWG conductors, 12 AWG EGC Upsized for voltage drop: 10 AWG conductors Required EGC: 10 AWG (proportionally increased per 250.122(B))
Common Violations
- Improper EGC sizing - Using undersized equipment grounding conductors
- Missing bonding jumpers - Not bonding metallic raceways and enclosures
- Improper electrode connections - Poor connections to grounding electrodes
- Missing intersystem bonding - Not providing bonding for other systems
Interactive Tools
Calculator tools will be available in a future update.
Related Code Sections
- Article 680 - Swimming Pools, Fountains, and Similar Installations
- Article 517 - Health Care Facilities
- Article 547 - Agricultural Buildings
- Table 250.66 - Grounding Electrode Conductor Sizing
- Table 250.122 - Equipment Grounding Conductor Sizing
Study Questions
- What is the minimum size grounding electrode conductor for a 400A service with 600 kcmil conductors?
- When must equipment grounding conductors be increased in size?
- What grounding electrodes must be bonded together when present?
- What is the difference between grounding and bonding?
This article summary is based on the 2023 National Electrical Code. Always consult the current adopted code in your jurisdiction and verify with local authorities having jurisdiction.