NEC 314.16 - Number of Conductors in Outlet, Device, and Junction Boxes
Educational Notice: This content provides interpretations of NEC 314.16. For official code text, please refer to NFPA 70 - National Electrical Code.
Overview
NEC 314.16 is one of the most frequently referenced code sections in electrical work. It establishes the maximum number of conductors permitted in outlet, device, and junction boxes based on the box volume and conductor size.
Box Fill Calculation Method
Step 1: Determine Box Volume
Use the marked volume on the box or refer to Table 314.16(A) for standard metal boxes.
Step 2: Count All Items
Each item in the box counts toward the fill calculation:
Conductor Count (314.16(B)(1))
- Each conductor = 1 count (based on largest conductor size in box)
- Conductors originating outside the box and terminating inside = 1 count each
- Conductors passing through without splice = 1 count each
- Looped conductors (unbroken) = 2 counts
Equipment Grounding Conductors (314.16(B)(5))
- All equipment grounding conductors = 1 count total (regardless of number)
- Based on largest equipment grounding conductor in the box
Cable Assembly Clamps (314.16(B)(2))
- One or more cable clamps = 1 count total
- Based on largest conductor in the box
Support Fittings (314.16(B)(3))
- Each fixture stud or hickey = 1 count
- Based on largest conductor in the box
Device or Equipment (314.16(B)(4))
- Each yoke or strap = 2 counts
- Based on largest conductor connected to the device
Safety Alert: Overfilled boxes can cause conductor damage, poor connections, and fire hazards. Always verify calculations before installation.
Volume Allowances per Conductor
Conductor Size | Volume per Conductor |
---|---|
18 AWG | 1.50 cubic inches |
16 AWG | 1.75 cubic inches |
14 AWG | 2.00 cubic inches |
12 AWG | 2.25 cubic inches |
10 AWG | 2.50 cubic inches |
8 AWG | 3.00 cubic inches |
6 AWG | 5.00 cubic inches |
Common Metal Box Volumes
4-inch Square Boxes
Depth | Volume | Max #14 | Max #12 | Max #10 |
---|---|---|---|---|
1¼" | 12.5 cu in | 6 | 5 | 4 |
1½" | 15.5 cu in | 7 | 6 | 5 |
2⅛" | 21.0 cu in | 10 | 8 | 7 |
4⅛-inch Square Boxes
Depth | Volume | Max #14 | Max #12 | Max #10 |
---|---|---|---|---|
1¼" | 14.0 cu in | 7 | 6 | 5 |
1½" | 16.5 cu in | 8 | 7 | 6 |
2⅛" | 24.5 cu in | 12 | 10 | 8 |
Single Gang Device Boxes
Size | Volume | Max #14 | Max #12 | Max #10 |
---|---|---|---|---|
3×2×2½" | 10.5 cu in | 5 | 4 | 4 |
3×2×2¾" | 12.5 cu in | 6 | 5 | 4 |
3×2×3½" | 14.0 cu in | 7 | 6 | 5 |
Calculation Examples
Example 1: Basic Outlet Box
Box: 4×4×1½" (15.5 cu in) Contents:
- 2 #12 THWN conductors (hot, neutral)
- 1 #12 equipment grounding conductor
- 1 duplex receptacle
- Cable clamps present
Calculation:
- Conductors: 2 × 2.25 = 4.5 cu in
- Grounding: 1 × 2.25 = 2.25 cu in
- Device: 2 × 2.25 = 4.5 cu in
- Clamps: 1 × 2.25 = 2.25 cu in
- Total: 13.5 cu in ≤ 15.5 cu in ✓
Example 2: Switch Box with Multiple Circuits
Box: 4×4×2⅛" (21.0 cu in) Contents:
- 4 #12 THWN conductors (2 hots, 2 neutrals)
- 2 #12 equipment grounding conductors
- 2 single-pole switches
- Cable clamps present
Calculation:
- Conductors: 4 × 2.25 = 9.0 cu in
- Grounding: 1 × 2.25 = 2.25 cu in
- Devices: 4 × 2.25 = 9.0 cu in (2 switches × 2 counts each)
- Clamps: 1 × 2.25 = 2.25 cu in
- Total: 22.5 cu in > 21.0 cu in ✗
Solution: Use larger box (24.5 cu in minimum)
Example 3: Junction Box
Box: 4⅛×4⅛×2⅛" (24.5 cu in) Contents:
- 6 #12 THWN conductors (3 circuits spliced)
- 3 #12 equipment grounding conductors
- Wire nuts (no additional count)
- No clamps (MC cable with built-in connectors)
Calculation:
- Conductors: 6 × 2.25 = 13.5 cu in
- Grounding: 1 × 2.25 = 2.25 cu in
- Total: 15.75 cu in ≤ 24.5 cu in ✓
Special Considerations
Nonmetallic Boxes
- Must be marked with their volume
- Same calculation method applies
- Cannot exceed marked volume
Conduit Bodies
- Limited conductor splicing allowed
- Must comply with 314.16 when containing splices
- Different rules for straight-through conductors
Mixed Conductor Sizes
- Use the largest conductor size for all calculations
- Example: Mix of #12 and #14 = use #12 (2.25 cu in) for all counts
Pro Tip: When in doubt, use a larger box. The additional cost is minimal compared to the safety benefits and ease of installation.
Common Violations
- Overcrowded boxes - Most common NEC violation
- Incorrect conductor counting - Not counting all items properly
- Using unmarked box volumes - Assuming volume without verification
- Ignoring equipment grounding conductors - Forgetting the single count rule
Interactive Calculator
Calculator tools will be available in a future update.
Related Sections
- Table 314.16(A) - Metal Box Volume Requirements
- Table 314.16(B) - Volume Allowance per Conductor
- 314.17 - Conductors Entering Boxes
- 314.28 - Pull and Junction Box Sizing
Based on NEC 2023. Always verify with local jurisdiction requirements.